Modules of special design with a useful volume of 20 liters and 30 liters are designed for long-term storage and extinguishing with gaseous fire extinguishing agents (GOTV) of class A, B, C fires and electrical equipment under voltage (the voltage at which it is possible to extinguish without turning off the protected equipment must correspond to requirements of NTD for GOTV).
They are used for fire protection of premises and equipment, in a modular design, for volumetric fire extinguishing. Structurally, the modules are metal vessels in the shape of an ellipsoid. There is a metal fastener at the top of the vessels.
In the neck of the vessels there is a shut-off and starting device with an electromechanical stimulator (hereinafter referred to as EMP), a pressure indicator (pressure gauge), a safety membrane and a pressure alarm device (hereinafter referred to as SDS). The module cylinders are painted white.
The modules are not intended for use in hazardous areas.
The modules are manufactured in the “UHL” climatic version, placement category 4 according to GOST 15150, for operation at ambient temperatures from -10 °C to plus 50 °C and relative humidity no more than 80% at a temperature of 15 °C. Package Included:
Gas fire extinguishing module assembled with control system;
Bracket for ceiling mounting (bracket for wall mounting – upon request);
Electro-mechanical starting device (EMD);
Pressure gauge;
Pressure alarm;
Passport combined with instruction manual;
Passport for the cylinder;
Standard cardboard packaging.
Peculiarities:
Modules of special design MGP-20 “SMD” and MGP-30 “SMD” use a locking and starting device (ZPU) from Rotarex, which has three types of triggering:
Main (automatic);
Manual ;
Autonomous – due to the destruction of the ZPU thermal lock flask under the influence of a temperature exceeding 68˚C.
1. The maximum operating pressure of the module is 2.5 MPa – allows you to refill two types of GOTV Freon 125 and Freon 227EA.
2. The module has a greater safety margin.
3. The service life of the cylinder until the first re-examination is 15 years.
4. When using a suspended GFFE module, it comes out practically without any residue.
5. Due to the suspended design, it saves space on the floor.
6. There are no costs for materials and installation work for pipework.
7. The module is a reusable device.
The manufacturer can make changes to the module design while maintaining its basic operational parameters.
Module parameters | Module type | |
IHL-20 “SMD” (25-20-20) | IHL-30 “SMD” (25-30-20) | |
Module volume, l | 20 | thirty |
Working pressure MPa (kgf/cm2) | 2.5 (25.5) | |
Test pressure, MPa (kgf/cm2) | 3.75 (38.3) | |
Propellant gas pressure, MPa (kgf/cm2) | 1.6 (16.3) | |
Actuation pressure of the membrane safety device, MPa (kgf/cm2) | 3.4(34.7) ± 0.17 | |
Type of purchased locking and starting device (BrandSys LLC, Yekaterinburg) | ZPU “ROTAREX” 20/4.2 (M30x1.5) | |
Diameter of the nominal bore of the control unit, mm | 20 | |
External diameter of the module, D, mm | 408±5 | |
Height of assembled module, L, mm | 410±5 | 488±5 |
Cylinder type | 100A.20.01 | 100A.30.01 |
Cylinder body material. | Carbon or alloy steel Corrosion resistant steel |
|
Thread in the neck of the cylinder, mm | M30x1.5 | |
Weight of the empty module, taking into account the spare parts, kg | 15.1±0.2 | 18.4±0.2 |
Release time of 95% GFTS by weight, s, no more | 10 | |
Residue of GFFS, no more than % by weight of GFSF | 0.5 | |
Operating temperature, °C | minus 20 °С to plus 50 °С | |
Service life before first re-examination, years | 15 | |
Response resource, no less than times | 10 | |
Electromechanical stimulator with a powder charge (Pusher PT-5, TU 7287-269-07513406-2008, Murom Instrument-Making Plant JSC) | PT-5 (1 piece) | |
Electrical resistance, Ohm | 2÷4.5 | |
PU network testing current, A, no more (within 5 minutes) | 0.05 | |
Operation voltage, V | 6.0÷30 | |
Operation current, A, not less | 0.5 | |
Starting pulse supply time, s | 0.01±0.001 | |
Refillable GOTV | Freon-227ea, Freon-125, Novec 1230 | |
Maximum fill factor, kg/l | 1.1 – (Freon-227ea); 0.9 – (Freon-125); 1,2 – (FK-5-1-12). |
|
ATTENTION! The PT-5 pusher is a single-use device. Cannot be disassembled, repaired or serviced. |